MV power cable
Tags : Electrical Wire,Flat Electrical Cables,PVC Insulated and PVC sheathed Flat cable
Summary: Single Core BV Electrical Wire 1.5mm 2.5mm 4mm 6mm With PVC Sheath Copper Conductor, used for separate earth conductors, switchboard and control panel wiring
Description
PVC Insulated Single-core Wire Construction:
Conductor:
Class 1 solid plain copper
Class 2 stranded plain copper
Insulation:PVC(Polyvinyl Chloride)
Electrical characteristics:
Rated voltage Uo/U (Um) : 300/500V; 450/750V
Test voltage: 2000V(300/500V); 2500V(450/750V)
Standards:
300/500V---60227 IEC 05(BV) / GB/T5023.3-2008
450/750V---60227 IEC 01(BV) / GB/T5023.3-2008
Physical features:
Bending radius: 15 x Ø
Service temperature:+70℃,+90℃,105℃ available
Insulation resistance: 10 MΩ x km
PVC Insulated Single-core Wire Application: For use in conduit and fixed,protected installation in switchgear, lighting, also for building wiring and the internal wiring of appliances and apparatus.
Packing: 100m per roll (per coil or plastic reel, as your request)
Specifications
PVC Insulated Single-core Wire Data Sheet 300/500V
Core number/sectional area(mm²) | Core no./diameter(mm) | Outer diameter(mm) | Weight(kg/km) | 20℃conductor resistance(Ω/km) |
1×0.5 | 1/0.80 | 2.3 | 8.5 | 36.0 |
1×0.75(A) | 1/0.97 | 2.3 | 8.5 | 36.0 |
PVC Insulated Single-core Wire Data Sheet 300/500V
Core number/sectional area(mm²) | Core no./diameter(mm) | Outer diameter(mm) | Weight(kg/km) | 20℃conductor resistance(Ω/km) |
1×0.5 | 1/0.80 | 2.3 | 8.5 | 36.0 |
1×0.75(A) | 1/0.97 | 2.3 | 8.5 | 36.0 |
Remarks: Flame retardant, fire resistance (adopt mica tape), low smoking and Halogen free, or other property are available.
ZR cable (flame retardant cable) is the kind of cable with PVC insulation built mixed with fire prevention additive to make it have the capability of preventing or retarding flame spread during combustion.
NH cable (fire resistant cable) is the kind of cable built with a layer of mica tape. Even if the plastic skin is burnt out, refractory layer will help not cause short circuit. When wiring, cut off the refractory layer at the wire head.
LSZH、LSOH、LS0H、LSFH or OHLS cable(Low smoke zero halogen cable) is cable with insulation or outer sheath built using low smoke zero halogen free material to help reduce toxic and corrosive gases produced during combustion.
Termite-proof cable is the cable built with insulation or outer sheath mixed with a kind of materials to prevent termite biting the cable.